Series | AI | |
| • Instead of the pulse signal, an analogue current signal 4...20 mA is provided by installing an internal transducer onto the suitable flow sensor | |
Technical data | ||
Output signal | 4...20 mA | |
Accuracy | ±1.25 % of reading* | |
Current limit | Approx. 26 mA | |
Scaling | Different flow ranges, see order code flow sensor other scaling possible from 10 pieces and above | |
Power supply | 18...30 VDC | |
Max. current consumption | 30 mA | |
Max. burden | 250 Ω against GND | |
Residual ripple | 0.2 mA (peak to peak) over the entire range | |
Type | 3 wire, galvanically not separated, common GND of power supply and output signal | |
Electrical connection | 4 pin plug connector, M12 x 1 | |
Degree of protection EN 60529 | IP54 | |
Max. medium temperature | Dependent on the maximum temperature of the used flow sensor, not exceeding 80 °C | |
Casing material | Plastic PA | |
Order code | See order code series VT |
* Additionally to respective accuracy of turbine flow sensor
문의 031)243-1035
FAX 031)243-1025