본문 바로가기 주메뉴 바로가기

제품소개

HOME > 제품소개 > Level > 레벨스위치

레벨스위치

레벨스위치

ULS-53 / 초음파형

  • 제조사 : Dinel, s.r.o
  • 제조국 : Czech Republic
•오염수, 배수조 등 액체 레벨측정
•마그네틱펜으로 세밀한 세팅가능
•LED표시기능
•방폭 옵션
DOWNLOAD
제품목록

제품사양

 Technical specifications

 Measuring range 1)

 ULS–53_–01–_

 ULS–53_–02–_

 ULS–53_–06–_

 ULS–53_–10–_

 ULS–53_–20–_

 ULS–53_–01–_

 ULS–53_–02–_

 ULS–53_–06–_

 ULS–53_–10–_

 ULS–53_–20–_

 Supply voltage

 ULS–53N–_ _–_ 

 ULS–53Xi–_ _ –_–S

 18 ... 36 V DC

 18 ... 30 V DC

 Current supply

 ULS–53N–_ _ –_–P 

 ULS–53_–_ _ –_–S

 max. 12 mA

 disconnected 4 mA / connected 20 mA

 Current output 

 

 Voltage output

 ULS–53N–_ _ –_–P 

 

 ULS–53_–_ _ –_–S

 PNP transistor with an open collector 

   (max. switch current 300 mA) 

 two-state current switch 4 mA / 20 mA

 Resolution

 < 1 mm

 Accuracy

 (within the total range)

 ULS–53_–01 in area0,1–0,2 m / 0,2–1,0 m

 ULS–53_–02; –06

 ULS–53_–10; –20

 0,3 % / 0,2 % 

 0,15 %

 0,2 %

 Temperature error

 max. 0,04% / K

 Beam width (-3 dB)

 ULS–53_–01–_ ; 02–_ ; 10–_

 ULS–53_–06–_

 ULS–53_–20–_

 10° 

 14° 

 12°

 Ambient temperature range

 ULS–53_–01–_ ;  02–_ ; 06–_ 

 ULS–53_–10–_ ;  20–_

 -30 ... +70°C 

 -30 ... +60°C

 Measuring period

 ULS–53_–01–_ ; 02–_

 ULS–53_–06–_

 ULS–53_–10–_

 ULS–53_–20–_

 0,6 s 

 1,0 s 

 1,8 s 

 5,0 s

 Averaging

 4 measurement 3)

 Short time temperature stress resistance

 +90°C / 1 hod.

 Max. operation overpressure (on transmission surface)

 0,1 MPa

 Max. internal values 2) (for the Xi version only)

 Ui=30 V DC; Ii=132 mA; Pi=0,99 W; Ci=370 nF; Li=0,9 mH

 Failure indication

 echo failure – basic mode

 echo failure – inverse mode

 level in dead zone 4) – basic mode 

 level in dead zone 4) – inverse mode

 3,75 mA / 0 V 

 22 mA / 10,5 V 

 22 mA / 10,5 V 

 3,75 mA / 0 V

 Protection class

 ULS-53_-__-_-_-_- T 

 ULS-53_-__-_-_- G-M, L

 IP67

 ULS-53_-__-_-_- C-M, L

 IP67 5)

 ULS-53_-__-_-_- B-M, L 

 ULS-53_-__-_-_- H-M, L

 IP68

 Recommended cable

 PVC 2 x 0,75 mm2 (3 x 0,5 mm2)

 Maximal current output load resistance

 at U = 24 V DC 

 at U = 22 V DC 

 at U = 20 V DC

 Rmax= 270 Ω

 Rmax=180 Ω

 Rmax=90Ω

 Minimal voltage output load resistance

 Rmin>1kΩ

 Delay between supply power rise time and first measurement

 ULS–53_–01–_ ; 02–_ ; 06–_ 

 ULS–53_–10–_; 20–_

 5 s 

 9 s

 Process connection

 ULS–53_–01–_

 ULS–53_–02–_

 ULS–53_–06–_

 ULS–53_–10–_

 ULS–53_–20–_

 thread G ¾‘‘

 thread G 1‘‘

 thread G 1½‘‘

 thread G 2¼‘‘ 

 aluminium alloy flange

 Weight

 ULS–53_–01–_

 ULS–53_–02–_

 ULS–53_–06–_

 ULS–53_–10–_

 ULS–53_–20–_

 0,20 kg 

 0,20 kg 

 0,25 kg 

 0,65 kg 

 2,80 kg

1)  In case the level of bulk-solid materials is measured, the measurement range is reduced.

2)  Allowed pressure range in the zone 0: 80 ... 110 kPa.

3)  From the last six measurements are taken out extreme values MAX and MIN, then the remaining four measurement was performed arithmetic average.

4)  Dead zone = blind zone = blocking zone.

5)  Protection class IP68 can be achieved when a special connector is used.

ULS-53-dat-3.3




문의 031)243-1035
FAX 031)243-1025
sales@gms-korea.com