Series | VE | ||
• Wide set point range and precise set point adjustment • Safe monitoring of lowest flow rates, fail safe • Optical signalling by 2 LEDs | |||
Technical data | DN 15 | DN 25 | DN 40 |
Set point range (with decreasing flow) / accuracy | 0.5...29.5 l/min / ±2 % of set point + accuracy of turbine flow sensor | 3...100 l/min / ±4 % of set point + accuracy of turbine flow sensor | 7...275 l/min / ±6 % of set point + accuracy of turbine flow sensor |
Set point adjustment | 16 different set points selectable | ||
Output / max. contact rating | Only switching output: Electrically insulated contact, opens in the case of lack of flow Max. contact rating 125 VAC / DC, 100 mA Switching output and pulse output Switching output against power supply Max. contact rating 100 mA Pulse output: flow-proportional frequency signal NPN, max. 100 mA | ||
Switching hysteresis | 0.5 l/min | 2...5 l/min | 3...35 l/min |
Power supply | 12...24 VDC | ||
Current consumption | Max. 25 mA | ||
Degree of protection | IP54 with closed sleve and connected socket | ||
Casing | Plastic PA, transparent | ||
Display, internal | LED yellow = ok , LED red = alarm | ||
Max. medium temperature | Dependent on the maximum temperature of the used flow sensor, not exceeding 80 °C | ||
Electrical connection | 4 pin plug connector, M12 x 1 | ||
Order code | See order code series VT |
문의 031)243-1035
FAX 031)243-1025
sales@gms-korea.com